The leading ignition protection type is crucial for the electrical connection of a pressure sensor with explosion protection. It does not necessarily must be the one with the stricter requirements. This applies, for example, for the UHP pressure transducers of the WU series from WIKA. They have been designed for use in semiconductor production.
Explosion protection can be an indispensable safety precaution there. This is due to the substances required for manufacturing include highly flammable gases. Consequently, there exists a threat of an explosive atmosphere forming.
Explosion protection concept
UHP pressure transducers for such processes should be made with the corresponding safety. As well as their small design and specific process connections, the models WUC-1x and WU-2x have a thorough explosion protection concept. The marking of the instruments provides information on this:
II 3G Ex ec ic IIC T6/T5/T4 Gc X
The abbreviations listed in them mean, in greater detail:
II 3G:
Equipment group 2 (all areas except mining), may be used in zone 2 (rare and short-term Ex atmosphere).
Ex ec ic:
Ignition protection types ?ec? (increased safety) and ?ic? (intrinsically Sick And Tired ).
?Ex ec? has replaced the ignition protection type ?Ex nA? (non-sparking) because the start of 2022. However, this does not affect the Ex concept of the instruments.
IIC:
Explosion group (here: gases, resistive ignition energy of 40 �J, suitable for hydrogen/acetylene).
T6/T5/T4:
Temperature classes. T6 as the highest requirement means a maximum permissible surface temperature in the Ex environment < 85 �C (max. surface temperature of the WUC-1x and WU-2x: 40 �C).
Gc:
?Equipment Protection Level? (EPL) for zone 2 per IEC 60079-0
X:
Specific requirements which are listed in the operating instructions (for instance, the best mating connector).
?ec? may be the leading ignition protection type
It is noticeable that the marking contains two ignition protection types. However, only one is relevant for the electrical connection: the best ignition protection type. In the case of the pressure transducers from the WU series, it is the Ex ec (Ex nA around 2022) mentioned first rather than the stricter Ex ic. This can also be seen in the connection values in the data sheet and operating instructions. Only the specification of the utmost supply voltage UN = 30 V, which is also stated in the IECEx certificate, is relevant here.
What does the classification ?Ex ic? are a symbol of? It only pertains to the potentiometer of the transducer. The resistive component has an intrinsically safe circuit and can therefore be adjusted to improve zero drift during operation. Within their overall form, the WU models do not require an intrinsically safe circuit. However, they must never be disconnected from the circuit during operation or when an Ex atmosphere is present.